Spectron-101-R-Exd-A Heat Detector
THE HEAT DETECTOR IS DESIGNED TO DETECT FIRES ACCOMPANIED BY RELEASE OF A BIG AMOUNT OF HEAT
- Spectron-101-R-Exd-A
Used in hazardous areas zones 1 and 2 of enclosed facilities. The sensitive element of the detector can be immersed in tanks and pipelines in hazardous areas zone 0. Explosion protection marking 1Ex db [ia Ga] IIC T6…T4 Gb X / Ex tb [ia Da] IIIC T85ºC…T135ºC Db X, where the X sign in the explosion protection marking means that during operation of the detector the sensor tube should be protected from mechanical shock |
|
Operating modes |
Rate of Rise; Rate of Rise & Fixed Heat; |
Temperature range of the electronic unit |
from -75 to +85 ºС |
Sensor response temperature |
-75 ÷ +150 ºС |
Temperature classes (selected by the user by setting the appropriate Rt resistor) |
A1, A2, А3, B, C, D, E A1R, A2R, А3R,BR, CR, DR, ER |
ATTENTION. The model of cable glands must be specified when adding to the specification and ordering the equipment. Cable glands are not included in the price of the equipment. Full information on cable glands is available on the CABLE GLAND page of our website . If you have any questions about the correct selection of the type of cable gland, you can contact the technical support service by phone. |
|
Wiring |
|
Ingress Protection by the housing in accordance with GOST 14254 |
|
|
|
Specialized program Spectron-OPS-AutoCAD for easier designing |
|
The warranty period of is 18 months from the date of commissioning, but not more than 24 months from the date of manufacturing. |
|
Spectron-101-R heat detectors are listed in the MTR “Gazprom” OJSC Stock item identification guide. |
|
"Spectron-101-R-Exd-A" is the commercial name of the detector, corresponds to the "IP101 Spectron-R" name in the certificate |