Spectron-601-S Series Flame Detector
UV/IR FIRE ALARM FLAME DETECTOR, HIGHLY IMMUNE TO FALSE ALARMS, DOESN’T REACT TO WELDING
Explosion-proof:
-
Spectron-601-Exi-S
-
Spectron-601-Exi-S-M
-
Spectron-601-Exi-S-N
-
Spectron-601-Exm-S
-
Spectron-601-Exm-S-M
-
Spectron-601-Exm-S-N
General industrial:
-
Spectron-601-S
-
Spectron-601-S-M
-
Spectron-601-S-N
-
Spectron-601-S-E
S2000-Spectron-607-Exi
Addressable: S2000-Spectron-607-Exi and S2000-Spectron-607 work in DPLS loop with S2000-KDL or S2000-KDL-2I
PARAMETERS OF EX-PROOF DETECTORS |
|||
Spectron-601-Exi-S - type of explosion protection is intrinsically safe electrical circuit. Explosion protection marking 0ExiaIICT4 X allows the detector to be used in hazardous areas of enclosed facilities and outdoor installations. Hazardous areas classes are Zone 0, 1 and 2. An intrinsically safe circuit is required to connect an intrinsically safe detector. The detector is connected to an explosion-proof control panel with an intrinsically safe output or to a general industrial control panel through an intrinsically safe barrier. Manufacturer recommended IS barriers:
|
|||
Spectron-601-Exm-S - type of explosion protection is encapsulation in a compound. Explosion protection marking 1Ex mb IIC T6 Gb X allows the detector to be used in hazardous areas of enclosed buildings and outdoor installations. Hazardous areas classes are Zones 1 and 2. An intrinsically safe circuit is not required to connect a detector with the encapsulated within a compound type of protection. Cables have to be laid considering the requirements of the PUE (section 7.3) for electrical wiring in hazardous areas. |
|||
GENERAL PARAMETERS OF GENERAL INDUSTRIAL AND EXPLOSION-PROOF DETECTORS |
|||
Spectron-601-S series detectors are ultra-immune to strong optical noise. Detects manual arc and argon welding as false interference |
|||
Recommended for use in fire alarm systems and fire extinguishing systems in enclosed facilities and open installations |
|||
Circuit board of the device is equipped with a 3-stage lightning and surge protector, which allows using it without additional equipment for overvoltage protection. | |||
Housing of Spectron-601-S(-E) and Spectron-601-Exm/Exi-S detectors is made of high-strength ABS plastic |
|||
Housing of Spectron-601-S-M and Spectron-601-Exm/Exi-S-M detectors is made of galvanized steel |
|||
Housing of Spectron-601-S-N and Spectron-601-Exm/Exi-S-N detectors is made of stainless steel AISI 321 |
|||
The maximum flame detection range according to GOST R 53325-2012 is 30 meters to TP5 and TP6. |
|||
For facilities with harsh operating conditions the detector is provided with the sensitivity modes Near/Far switching option. Detection range in the Near mode is 12 m, and 30 m in the Far mode. |
|||
The field of view of Spectron-601-S series is 90º in the vertical, horizontal and all inclined planes. |
|||
Minimal response time, seconds |
6; 22*
(user changeable) |
||
The transition of the detector from the Alarm mode to the Normal mode is carried out by disconnecting the power supply for at least 2 seconds |
|||
The automatic transition of the detector from the Alarm mode to the Normal mode is activated by switching on the "Flame source control" function in the detector's service menu. |
|||
|
|||
Modifications of the Spectron-601-S series flame detectors with "E" letter denotes an individual setting for a specific facility with harsh operating conditions |
|||
Spectron Flame Detector |
601-Exi-S-M/N |
601-Exm-S-M/N |
601-S |
Wiring |
|
|
|
Self-testing |
|
|
![]() |
Ingress Protection by the housing in accordance with GOST 14254, not less |
|
|
|
|
|
No |
|
Surface-mounting boxes recommended by the manufacturer for connecting the detector |
Spectron-MK-04-Exi |
Explosion Proof Boxes Ехе or Ехd |
Spectron-MK-04 |
Specialized program Spectron-OPS-AutoCAD for easier designing |
|||
The warranty period of is 18 months from the date of commissioning, but not more than 24 months from the date of manufacturing. |
|||
To purchase S2000-Spectron-607-Exi and S2000-Spectron-607 please contact "NVP Bolid" |
|||
Spectron-601-S series flame detector is listed in the MTR “Gazprom” OJSC Stock item identification guide. |
* - parameter with factory setting.
or using e-mail: support@spectron-ops.ru