Spectron-601-S Series Flame Detector


Package price:
27 510.00  rub.
-
+
Package and accessories:
Modification:
Sun visor:
0.00 rub.
Switching box:
0.00 rub.
Protective device:
0.00 rub.
 
You can FIND INFORMATION ON CABLE ENTRY and add a test transmitter, a power supply, and a spark protection barrier to commercial offer in the section Accessories
КорзинаГДЕ КУПИТЬ

UV/IR FIRE ALARM FLAME DETECTOR, HIGHLY IMMUNE TO FALSE ALARMS, DOESN’T REACT TO WELDING

Explosion-proof:

  • Spectron-601-Exi-S
  • Spectron-601-Exi-S-M
  • Spectron-601-Exi-S-N
  • Spectron-601-Exm-S
  • Spectron-601-Exm-S-M
  • Spectron-601-Exm-S-N

General industrial:

  • Spectron-601-S
  • Spectron-601-S-M
  • Spectron-601-S-N
  • Spectron-601-S-E

S2000-Spectron-607-Exi

Addressable: S2000-Spectron-607-Exi and S2000-Spectron-607 work in DPLS loop with S2000-KDL or S2000-KDL-2I

PARAMETERS OF EX-PROOF DETECTORS

Spectron-601-Exi-S - type of explosion protection is intrinsically safe electrical circuit. Explosion protection marking 0ExiaIICT4 X allows the detector to be used in hazardous areas of enclosed facilities and outdoor installations. Hazardous areas classes are Zone 0, 1 and 2.

An intrinsically safe circuit is required to connect an intrinsically safe detector.

The detector is connected to an explosion-proof control panel with an intrinsically safe output or to a general industrial control panel through an intrinsically safe barrier. Manufacturer recommended IS barriers:

  • Spectron-IB-01 – 12 V/500 mA, for conventional detector with 4-wire connection;
  • Spectron-IB-02 – 24 V/100 mA for conventional detector with 2-wire connection to the alarm control panel;
  • S2000-Spectron-IB - for an addressable detector when connected in the DPLS loop

Spectron-601-Exm-S - type of explosion protection is encapsulation in a compound. Explosion protection marking 1Ex mb IIC T6 Gb X allows the detector to be used in hazardous areas of enclosed buildings and outdoor installations. Hazardous areas classes are Zones 1 and 2.

An intrinsically safe circuit is not required to connect a detector with the encapsulated within a compound type of protection. Cables have to be laid considering the requirements of the PUE (section 7.3) for electrical wiring in hazardous areas.

GENERAL PARAMETERS OF GENERAL INDUSTRIAL AND EXPLOSION-PROOF DETECTORS

Spectron-601-S series detectors are ultra-immune to strong optical noise. Detects manual arc and argon welding as false interference

Recommended for use in fire alarm systems and fire extinguishing systems in enclosed facilities and open installations

Circuit board of the device is equipped with a 3-stage lightning and surge protector, which allows using it without additional equipment for overvoltage protection.

Housing of Spectron-601-S(-E) and Spectron-601-Exm/Exi-S detectors is made of high-strength ABS plastic

Housing of Spectron-601-S-M and Spectron-601-Exm/Exi-S-M detectors is made of galvanized steel

Housing of Spectron-601-S-N and Spectron-601-Exm/Exi-S-N detectors is made of stainless steel AISI 321

The maximum flame detection range according to GOST R 53325-2012 is 30 meters to TP5 and TP6.

For facilities with harsh operating conditions the detector is provided with the sensitivity modes Near/Far switching option. Detection range in the Near mode is 12 m, and 30 m in the Far mode.

The field of view of Spectron-601-S series is 90º in the vertical, horizontal and all inclined planes.

Minimal response time, seconds

6; 22*
(user changeable)

The transition of the detector from the Alarm mode to the Normal mode is carried out by disconnecting the power supply for at least 2 seconds

The automatic transition of the detector from the Alarm mode to the Normal mode is activated by switching on the "Flame source control" function in the detector's service menu.

  • The temperature range of the detector in plastic housing is -55 to +75 ºС.
  • The temperature range of the detector in metal housing is -55 to +85 ºС, remains operational with a brief increase in temperature up to +125 ºС

Modifications of the Spectron-601-S series flame detectors with "E" letter denotes an individual setting for a specific facility with harsh operating conditions

Spectron Flame Detector

601-Exi-S-M/N

601-Exm-S-M/N

601-S

Wiring

Self-testing

Ingress Protection by the housing in accordance with GOST 14254, not less

Type of explosion protection


Exi


Exm

No

Surface-mounting boxes recommended by the manufacturer for connecting the detector

Spectron-MK-04-Exi

Explosion Proof Boxes

Ехе or Ехd

Spectron-MK-04

Specialized program Spectron-OPS-AutoCAD for easier designing

The warranty period of is 18 months from the date of commissioning, but not more than 24 months from the date of manufacturing.

To purchase S2000-Spectron-607-Exi and S2000-Spectron-607 please contact "NVP Bolid"

Spectron-601-S series flame detector is listed in the MTR “Gazprom” OJSC Stock item identification guide.

* - parameter with factory setting.

Technical support: 8 800 500-10-73 (free call)